Inverters
An inverter in combination with a battery
system provides an uninterruptible AC supply. These units are developed
for applications where availability is a high priority, such as power
plants, switchgear, process installations and communication equipment.
The inverters are HF switched, which results in light, compact modules
that allow flexible configuration in 19” racks. High efficiency
gives low losses and a high yield on battery capacity.
For maximum availability,
inverters are equipped with a static switch for uninterrupted changeover
to an alternative AC supply in the event of overload. Inverter systems
are built up in 19” racks that include circuit breakers and a manual
bypass for safe, uninterrupted isolation of the system for scheduled
maintenance.
For
uninterruptible AC motor drives you should also see our UMD (uninterruptible
motor drive) products
 |
INVB inverter
Input voltage: 24-220
VDC
Output voltage: Standard;
230 VAC/50 Hz, Option; 115 VAC/60 Hz
Output power VA: 500,
1,000 och 2,000VA
The INVB inverter module has compact dimensions (19” 4HE)
a rugged construction, low weight and connections at the front
for easy installation and minimal space requirements.
Accessories
include a 19” rack for wall mounting, with built-in
manual bypass, circuit breaker, fuses and terminals for stationary
installation.
Read more |
 |
PCI10 inverter system
Input voltage: 48-220
VDC
Output voltage: Standard;
230 VAC/50 Hz, Option; 115 VAC/60 Hz
Output power VA: 4,000-48,000VA
The PCI10 inverter system is built up
using 4 kVA modules that can be connected in parallel for additional
capacity, availability and reliability up to a total output of
48 kVA. The system is housed in a floor cabinet with 19” rack containing manual bypass,
circuit breaker, fuses and terminals for stationary installation.
Read more |
How do I choose an inverter?
- Nominal voltage of battery system?
- Desired output voltage and power?
- Need for redundancy provided by
additional parallel unit (n+1 redundancy)?
- Power supply for three-phase
AC motor? Also see our UMD (uninterruptible motor drive) products.
| Inverter |
INVB |
PCI 10 |
| Topology |
HF-switch |
HF-switch |
| Static switch |
Yes |
Yes |
| AC-output voltage |
Single phase 230V 50Hz |
Single phase 230V 50Hz |
| |
Single phase 115V 60Hz |
Single phase 115V 60Hz |
| |
|
|
| DC-input voltage/output power |
|
|
| 220VDC |
500VA–2000VA |
4kVA–48kVA |
| 125/110VDC |
500VA–2000VA |
4kVA–48kVA |
| 48VDC |
500VA–2000VA |
4kVA–48kVA |
| 24VDC |
500VA–2000VA |
- |
| Can units be connected in parallel? |
No |
Yes |
|